We have recently had some experience with glass office partitions, which left us with some severe reservations about the appropriateness of relying on the Australian Standard (AS 1288) to deliver the appropriate glass thickness for this application.

 

The specification for the project required that all office partitions be capable of carrying 0.25 kPa live load (Standard APG Tickbook).  These requirements are met by the code (AS1288 1994 Table 5.5) but the client and builder (Lend Lease) were not at all happy with the flexibility of the resultant system.  The builder paid to stiffen many of the glass panels to provide what everyone perceived as a reasonable degree of stiffness.

 

We suggest that when specifying office partitions, a height/240 maximum deflection should be used in conjunction with the 0.25kPa live load.  If you have any specific concerns relating to the use, safety, patch fixings etc and require a structural engineer in Canberra ACT to steer you in the right direction call Mal Wilson from Advanced Structural Designs on (02) 61612171.

 