Glass
Office Partitions
We have
recently had some experience with glass office partitions, which left us with
some severe reservations about the appropriateness of relying on the Australian
Standard (AS 1288) to deliver the appropriate glass thickness for this
application.
The
specification for the project required that all office partitions be capable of
carrying 0.25 kPa live load (Standard APG Tickbook). These requirements are met by the code
(AS1288 1994 Table 5.5) but the client and builder (Lend Lease) were not at all
happy with the flexibility of the resultant system. The builder paid to stiffen many of the glass
panels to provide what everyone perceived as a reasonable degree of stiffness.
We suggest
that when specifying office partitions, a height/240 maximum deflection should
be used in conjunction with the 0.25kPa live load. If you have any specific concerns relating to
the use, safety, patch fixings etc and require a structural engineer in
Canberra ACT to steer you in the right direction call Mal Wilson from Advanced
Structural Designs on (02) 61612171.